Please address the following comments:
- Hydrant must be within 300’ of the building(s), measured as the truck drives (Commercial) Same clarification needed for the neighborhood Retail Store.
Please add a Fire & Life Safety Notes section to the plans with the following:
- Fire Hydrants to be installed per City of Wilmington ordinance and CFPUA Standards
- Contractor shall maintain an all-weather access for emergency vehicles at all times during construction
- New hydrants must be brought into service prior to combustible materials delivered to the job site
- Landscaping or parking cannot block or impede fire hydrants. A 3-foot clear space shall be maintained around the circumference of the hydrant
- Additional fire protection and/or accessibility requirements may be required due to any special circumstances concerning the project.
- Contractor shall submit a Radio Signal Strength Study for the commercial retail that demonstrates that existing emergency responder radio signal levels meet the requirements of Section 510 of the 2018 NC Fire Code.
Please contact Chris Walker at 343-3918 or email at chris.walker@wilmingtonnc.gov with any questions.
Please see attached for comments
Engineering has reviewed the plans for the Cottages at College Acres project submitted May 3, 2019 and offer the attached comments.