***SAME COMMENTS AS BEFORE
Your plan notes lead me to believe there is a sprinkler system. If so please illustrate the FDC location on the site plan. Also, if there is no sprinkler system please show a hydrant that meets the 300 ft. requirement for commercial buildings.
Address the following comments:
- Show all FDC locations on the plan.
- FDC must be on the front of the building unless otherwise approved.
- Hydrant must be within 300’ of the building(s), measured as the truck drives (Commercial)
- The type of Building Construction according to the International Building Code must be present on the plans. (Preferably the site data table)