Same commments as before:
- Show a hydrant within 500’ of all subdivision lots by road. It appears all lots on road F are not within 500' of a hydrant.
Please add the following Fire & Life Safety Notes to the Plan:
- Contractor shall maintain an all-weather access for emergency vehicles at all times during construction
- Landscaping or parking cannot block or impede the fire hydrants. A 3-foot clear space shall be maintained around the circumference of all hydrants
- Additional fire protection and/or accessibility requirements may be required due to any special circumstances concerning the project.