The plan indicates the use of 2 1/2" Siamese Connections for Remote FDC's. The City of Wilmington and the Fire Marshal's Office require all FDC's to be 5" Storz Connections.
Also, please add the following notes to the plan under either the General Notes (Utility Plan Sheet) or a new heading Fire & Life Safety Notes:
- Hydrant must be within 150' of the FDC. **
- The FDC must be within 40' of fire apparatus placement. **
- Landscaping or parking cannot block or impede the FDC or fire hydrants. A 3-foot clear space shall be maintained around the
circumference of the hydrant and FDC. **
- Contractor shall maintain an all weather access for emergency vehicles at all times during construction. **
- In addition to the standard comments, additional fire protection and accessibility requirements may be required
due to any special circumstances concerning the project. **
- Private Underground Fire Lines require a separate underground fire line permit from the Wilmington Fire and
Life Safety Division 910-343-0696 **
- All isolation valves within the “Hot Box” shall be electrically supervised. Please work closely with your fire
sprinkler and alarm installer in regards to running wire for tamper switch. **
** Comments must be on plans.
Contact Chris Walker at 343-3918 for questions or email at chris.walker@wilmingtonnc.gov
WILMINGTON TREATMENT –PARTIAL HOSPITALIZATION CENTER [TRC Plan Review #2]
Initial Review Note
All comments are based on adopted policy documents, specific City of Wilmington Land Development Code (CofW LDC) and City of Wilmington Technical Standards and Specifications Manual (CofWTSSM) requirements in effect at the time of this review. These have been noted after the comment as appropriate for your ease in further research.
The City Engineer may administratively approve dimensional variance requests per LDC Sec. 18-348. If the Applicant feels further interpretation is in order, please contact Transportation Planning directly to discuss in additional detail. Please apply for all administrative variances in writing, an email is acceptable or this may be included on the plan set. Please see Sec. 18-348 of the Land Development Code for the information required to process a variance request.
TECHNICAL STANDARDS – ACCESS (driveway, sidewalk, and sight distance):
6. The 50’ Access Easement Roadway and 24’ Wide Loop Roadway appears to be missing sections of Sidewalk (southern side of the Access Road and Eastern Side of the Loop Road).
7. Please show how the sidewalk gates will be activated/ opened. The sidewalk connections to the public sidewalk are shown with gates, which may need to be accessed for a security or evacuation event.
8. Provide the horizontal centerline radius for the 50’ Access Easement. This route will be used by the Fire and Rescue vehicles therefore a minimum R100’ centerline will be required.
9. The Carolina Beach Entrance was designated by City GIS as a private street entrance. Please show and apply the City’s 46’X46’ Sight Distance Triangle at this intersection on the site and landscaping plans.
[Sec.18-529(c)(3)CofW LDC] Add a note indicating that all proposed vegetation within sight triangles shall not interfere with clear visual sight lines from 30"-10'. [Sec.18-566 CofW LDC]
TECHNICAL STANDARDS – PARKING:
TECHNICAL STANDARDS – Barrier Free Design:
MISCELLANEOUS:
Please let me know if you have any questions or if I can be of further assistance as this development moves through the review process.
WILMINGTON TREATMENT –PARTIAL HOSPITALIZATION CENTER [TRC Plan Review #2]
Initial Review Note
All comments are based on adopted policy documents, specific City of Wilmington Land Development Code (CofW LDC) and City of Wilmington Technical Standards and Specifications Manual (CofWTSSM) requirements in effect at the time of this review. These have been noted after the comment as appropriate for your ease in further research.
The City Engineer may administratively approve dimensional variance requests per LDC Sec. 18-348. If the Applicant feels further interpretation is in order, please contact Transportation Planning directly to discuss in additional detail. Please apply for all administrative variances in writing, an email is acceptable or this may be included on the plan set. Please see Sec. 18-348 of the Land Development Code for the information required to process a variance request.
TECHNICAL STANDARDS – ACCESS (driveway, sidewalk, and sight distance):
6. The 50’ Access Easement Roadway and 24’ Wide Loop Roadway appears to be missing sections of Sidewalk (southern side of the Access Road and Eastern Side of the Loop Road).
7. Please show how the sidewalk gates will be activated/ opened. The sidewalk connections to the public sidewalk are shown with gates, which may need to be accessed for a security or evacuation event.
8. Provide the horizontal centerline radius for the 50’ Access Easement. This route will be used by the Fire and Rescue vehicles therefore a minimum R100’ centerline will be required.
9. The Carolina Beach Entrance was designated by City GIS as a private street entrance. Please show and apply the City’s 46’X46’ Sight Distance Triangle at this intersection on the site and landscaping plans.
[Sec.18-529(c)(3)CofW LDC] Add a note indicating that all proposed vegetation within sight triangles shall not interfere with clear visual sight lines from 30"-10'. [Sec.18-566 CofW LDC]
TECHNICAL STANDARDS – PARKING:
TECHNICAL STANDARDS – Barrier Free Design:
MISCELLANEOUS:
Please let me know if you have any questions or if I can be of further assistance as this development moves through the review process.