Per Patrick O'Mahony attached.
Please address the following comments:
- The type of Building Construction according to the International Building Code must be present on the plans. (Preferably the site data table)
Please add the following Fire & Life Safety Notes:
- Landscaping or parking cannot block or impede fire hydrants. A 3-foot clear space shall be maintained around the circumference of the hydrant
- Additional fire protection and/or accessibility requirements may be required due to any special circumstances concerning the project.
- Contractor shall submit a Radio Signal Strength Study for all commercial buildings that demonstrates that existing emergency responder radio signal levels meet the requirements of Section 510 of the 2018 NC Fire Code.
- All isolation valves within the “Hot Box” and between the “Hot Box” and the riser room, must be electrically supervised.