See attached for comments.
Please address the following:
- The type of Building Construction according to the International Building Code must be present on the plans. (Preferably the site data table)
- Show all FDC locations on final plan.
Please add the following Fire and Life Safety Notes to the plan:
- Hydrant must be within 150' of the FDC (measured as the truck drives for practical use)
- FDC must be within 40' of fire apparatus placement
- Private Underground Fire Lines require a separate underground fire line permit from the Wilmington Fire and Life Safety Division 910-343-0696
- Contractor shall maintain an all-weather access for emergency vehicles at all times during construction
- Landscaping or parking cannot block or impede fire hydrants. A 3-foot clear space shall be maintained around the circumference of the hydrant
- Additional fire protection and/or accessibility requirements may be required due to any special circumstances concerning the project.
- Contractor shall submit a Radio Signal Strength Study for all commercial buildings that demonstrates that existing emergency responder radio signal levels meet the requirements of Section 510 of the 2018 NC Fire Code.