Engineering has reviewed the TRC submittal for the Baker Luxury Collection project and offers the following comments
Please address the following comments:
- Hydrant must be within 300’ of the building(s), measured as the truck drives (Commercial)
- Fire Hydrants to be installed per City of Wilmington ordinance and CFPUA Standards
Please add the following FIRE & LIFE SAFETY notes to the plan:
- Contractor shall maintain an all-weather access for emergency vehicles at all times during construction
- New hydrants must be brought into service prior to combustible materials delivered to the job site
- Landscaping or parking cannot block or impede the FDC or fire hydrants. A 3-foot clear space shall be maintained around the circumference of the hydrant and FDC
- Additional fire protection and/or accessibility requirements may be required due to any special circumstances concerning the project.
- Contractor shall submit a Radio Signal Strength Study for all commercial buildings that demonstrates that existing emergency responder radio signal levels meet the requirements of Section 510 of the 2018 NC Fire Code.