- Hydrant must be within 300’ of the building(s), measured as the truck drives (Commercial)
- Fire Hydrants to be installed per City of Wilmington ordinance and CFPUA Standards
- Fire apparatus access road shall be no less than 20’ in width.
- Fire apparatus access road is greater than 150’. An approved fire apparatus turnaround must be provided.
- All exterior portions of the building must be within 150’ of a fire department access road. This is determined by location the fire apparatus stops in the parking area or access road.
- Type of Construction of Building according to the International Building Code must be present on the plans.
- Contractor shall maintain an all-weather access for emergency vehicles at all times during construction
- In addition to the standard comments, additional fire protection and accessibility requirements may be required due to any special circumstances concerning the project.