Field adjustments of tree protection based on actual site conditions/retraints will be critical for tree preservation. Coordinate with City Arborist.
No further comments.
Please address the following:
- The type of Building Construction according to the International Building Code must be present on the plans.(ex..TYPE I, II, III, IV)
Please add the following Fire & Life Safety notes to the plans: (Preferably a Fire & Life Safety Notes Section)
- New hydrants must be brought into service prior to combustible materials delivered to the job site
- Hydrant must be within 150' of the FDC (measured as the truck drives for practical use)
- FDC must be within 40' of fire apparatus placement
- Landscaping or parking cannot block or impede the FDC or fire hydrants. A 3-foot clear space shall be maintained around the circumference of the hydrant and FDC
- Additional fire protection and accessibility requirements may be required due to any special circumstances concerning the project.
- All isolation valves within the “Hot Box” shall be electrically supervised. Please work closely with your fire sprinkler and alarm installer in regards to running wire for tamper switch.