No further comments from planning
Please add the following Fire & Life Safety Notes to the plan:
- Hydrant must be within 150' of the FDC (measured as the truck drives for practical use)
- FDC must be within 40' of fire apparatus placement
- Landscaping or parking cannot block or impede the FDC or fire hydrants. A 3-foot clear space shall be maintained around the circumference of the hydrant and FDC
Please contact Chris Walker at 343-3918 or email at chris.walker@wilmingtonnc.gov with any questions.