We need to discuss the fire hydrant locations in relation to the FDC location. Please address the following:
- Fire Hydrants to be installed per City of Wilmington ordinance and CFPUA Standards
- Water flow analysis will be required to determine the correct water main size to meet sprinkler system demand and fire flow requirements
Please add the following Fire & Life Safety notes to the plan:
- Contractor shall maintain an all-weather access for emergency vehicles at all times during construction
- New hydrants must be brought into service prior to combustible materials delivered to the job site
- Hydrant must be within 150' of the FDC (measured as the truck drives for practical use)
- FDC must be within 40' of fire apparatus placement
- Landscaping or parking cannot block or impede the FDC or fire hydrants. A 3-foot clear space shall be maintained around the circumference of the hydrant and FDC
- In addition to the standard comments, additional fire protection and accessibility requirements may be required due to any special circumstances concerning the project.
- Private Underground Fire Lines require a separate underground fire line permit from the Wilmington Fire and Life Safety Division 910-343-0696
- All isolation valves within the “Hot Box” shall be electrically supervised. Please work closely with your fire sprinkler and alarm installer in regards to running wire for tamper switch.
CITY OF WILMINGTON POLICE FIRE & CITY TRAINING FACILITY [TRC Plan Review]
Initial Review Note
All comments are based on adopted policy documents, specific City of Wilmington Land Development Code (CofW LDC) and City of Wilmington Technical Standards and Specifications Manual (CofWTSSM) requirements in effect at the time of this review. These have been noted after the comment as appropriate for your ease in further research.
The City Engineer may administratively approve dimensional variance requests per LDC Sec. 18-348. If the Applicant feels further interpretation is in order, please contact Transportation Planning directly to discuss in additional detail. Please apply for all administrative variances in writing, an email is acceptable or this may be included on the plan set. Please see Sec. 18-348 of the Land Development Code for the information required to process a variance request.
BASE INFORMATION:
TECHNICAL STANDARDS – ACCESS (driveway, sidewalk, and sight distance):
2. Show and apply the City’s 20’x70’ sight distance triangle at each driveway on the site plan and landscaping plan. [Sec.18-529(c)(3)CofW LDC] Add a note indicating that all proposed vegetation within sight triangles shall not interfere with clear visual sight lines from 30"-10'. [Sec.18-556 CofW LDC]
TECHNICAL STANDARDS – PARKING:
TECHNICAL STANDARDS – Barrier Free Design:
7. The 6’ sidewalk as proposed adjacent to perpendicular parking spaces, does not meet ADA requirements. An allowance for a 2.5’ vehicle overhang must be considered. 4' of the sidewalk must remain clear for pedestrian use. [Chapter VII, Detail SD 15-13 CofWTSSM]
GENERAL NOTES TO ADD TO THE PLAN:
MISCELLANEOUS:
Please let me know if you have any questions or if I can be of further assistance as this development moves through the review process.