The 927 Military Cutoff Rd is a good address for the overall project address.
When the project is realeased for construction, please contact Michelle or Jim, to have the individual buildings, and any units, addressed.
Michelle.hutchinson@wilmingtonnc.gov
Jim.Sahlie@wilmingtonnc.gov
Thanks
RENAISSANCE MARKET [TRC Plan Review]
Initial Review Note
All comments are based on adopted policy documents, specific City of Wilmington Land Development Code (CofW LDC) and City of Wilmington Technical Standards and Specifications Manual (CofWTSSM) requirements in effect at the time of this review. These have been noted after the comment as appropriate for your ease in further research. The City Engineer may administratively approve dimensional variance requests per LDC Sec. 18-348. If the Applicant feels further interpretation is in order, please contact Transportation Planning directly to discuss in additional detail. Please apply for all administrative variances in writing, an email is acceptable or this may be included on the plan set. Please see Sec. 18-348 of the Land Development Code for the information required to process a variance request.
BASE INFORMATION:
NCDOT:
TECHNICAL STANDARDS – NEW ROADS:
TECHNICAL STANDARDS – ACCESS (driveway, sidewalk, and sight distance):
8. Provide additional dimensions for all the existing and proposed sidewalk and trail in the vicinity of the development on site plan.
9. Show the location of stop signs and directional arrows for the vehicular traffic maneuvering around the building/s.
10. Site plan shows the monument signs at the intersection of Military Cut-off Rd and the northern driveway, and at the corner of Sir Tyler Dr. Please verify that the signs do not interfere with Sight Distance.
Show and apply the City’s 20’x70’ sight distance triangle at each driveways and the City’s 46’x46’ sight distance triangle at Sir Tyler Drive corner intersection on the site plan and landscaping plan. [Sec.18-529(c)(3)CofW LDC] Add a note indicating that all proposed vegetation within sight triangles shall not interfere with clear visual sight lines from 30"-10'. [Sec.18-556 CofW LDC]
TECHNICAL STANDARDS – PARKING:
TECHNICAL STANDARDS – Barrier Free Design:
GENERAL NOTES TO ADD TO THE PLAN:
MISCELLANEOUS:
v Contact Traffic Engineering at 910-341-7888 to discuss street lighting options on the public ROW.
Please let me know if you have any questions or if I can be of further assistance as this development moves through the review process.
- Hydrant must be within 150' of the FDC. **
- The FDC must be within 40' of fire apparatus placement. **
- Show all FDC locations on final plan.
- FDC must be on the front of the building unless otherwise approved.
- Landscaping or parking cannot block or impede the FDC or fire hydrants. A 3-foot clear space shall be maintained around the circumference of the hydrant and FDC. **
- Hydrant must be within 300’ of the buildings. (Commercial)
- Water flow analysis will be required to determine the correct water main size to meet sprinkler system demand and fireflow requirements.
- Fire apparatus access road shall be no less than 20’ in width.
- Contractor shall maintain an all weather access for emergency vehicles at all times during construction. **
- All exterior portions of the building must be within 150’ of a fire department access road. This is determined by location the fire apparatus stops in the parking area or access road.
- Fire Hydrants to be installed per City of Wilmington ordinance and CFPUA Standards
- New Hydrants must be brought into service prior to combustible materials being delivered to the job site. **
- Type of Construction of Building according to the International Building Code must be present on the plans.
- In addition to the standard comments, additional fire protection and accessibility requirements may be required due to any special circumstances concerning the project. **
- Private Underground Fire Lines require a separate underground fire line permit from the Wilmington Fire and Life Safety Division 910-343-0696 **
- All isolation valves within the “Hot Box” shall be electrically supervised. Please work closely with your fire sprinkler and alarm installer in regards to running wire for tamper switch. **
** Comments must be on plans.
Contact Chris Walker at 343-3918 for questions or email at chris.walker@wilmingtonnc.gov